# Data point list for DLMS testing

[M failure 1]
name    = Communication status
query   = pe

# object <Station #>.<Class-ID>.<Media>.<Channel>.<selection-1>.<selection-2>.<selection-3>.<Unused 255>
# snobject <Station #>.<Short-Name-Id>

[X snobject 1.0x1778]
trend = 1min
name = Energie total A+
format = P:10
query = pe

[X snobject 1.0x03F0]
trend = 1min
name = Energie A+ Tarif 1
format = P:10
query = pe

[X snobject 1.0x1908]
trend = 1min
name = Energie total R+
format = P:10
query = pe

[X snobject 1.0x0710]
trend = 1min
name = Energie R+ Tarif 1
format = P:10
query = pe

[X snobject 1.0xD2F8]
trend = 1min
name = Leistungsmax. A+ Tarif 1
format = P:10
query = pe

[X snobject 1.0xD618]
trend = 1min
name = Leistungsmax. R+ Tarif 1
format = P:10
query = pe

[X snobject 1.0xCBF0]
trend = 1min
name = akt. Leistungsmittel A+
format = P:10
query = pe

[X snobject 1.0xCD80]
trend = 1min
name = akt. Leistungsmittel R+
format = P:10
query = pe

[X snobject 1.0xCBF8]
trend = 1min
name = letztes Leistungsmittel A+
format = P:10
query = pe

[X snobject 1.0xCD88]
trend = 1min
name = letztes Leistungsmittel R+
format = P:10
query = pe

[X object 1.3.1.1.32.7.0.255]
trend = 1min
name = Volt L1
format = P:10 F:0.01
query = pe

[X object 1.3.1.1.52.7.0.255]
trend = 1min
name = Volt L2
format = P:10 F:0.01
query = pe

[X object 1.3.1.1.72.7.0.255]
trend = 1min
name = Volt L3
format = P:10 F:0.01
query = pe

[X object 1.3.1.1.31.7.0.255]
trend = 1min
name = Amp L1
format = P:10
query = pe

[X object 1.3.1.1.51.7.0.255]
trend = 1min
name = Amp L2
format = P:10
query = pe

[X object 1.3.1.1.71.7.0.255]
trend = 1min
name = Amp L3
format = P:10
query = pe

[X object 1.3.1.1.91.7.0.255]
trend = 1min
name = Amp L0
format = P:10
query = pe

[X object 1.3.1.1.1.8.1.255]
trend = 1min
name = chn1, SL1 Active power+ (QI+QIV) int1 rate1
format = P:10
query = pe

[X object 1.3.1.1.1.8.2.255]
trend = 1min
name = chn1, SL1 Active power+ (QI+QIV) int1 rate2
format = P:10
query = pe

[X object 1.3.1.1.2.8.1.255]
trend = 1min
name = chn1, SL1 Active power (QII+QIII) int1 rate1
format = P:10
query = pe

[X object 1.3.1.1.2.8.2.255]
trend = 1min
name = chn1, SL1 Active power (QII+QIII) int1 rate2
format = P:10
query = pe

[X object 1.3.1.1.3.8.1.255]
trend = 1min
name = chn1, SLi Reactive power+ (QI+QII) int1 rate1
format = P:10
query = pe

[X object 1.3.1.1.3.8.2.255]
trend = 1min
name = chn1, SLi Reactive power+ (QI+QII) int1 rate2
format = P:10
query = pe

[X object 1.3.1.1.4.8.1.255]
trend = 1min
name = chn1, SLi Reactive power (QIII+QIV) int1 rate1
format = P:10
query = pe

[X object 1.3.1.1.4.8.2.255]
trend = 1min
name = chn1, SLi Reactive power (QIII+QIV) int1 rate2
format = P:10
query = pe



[M failure 2]
name    = Communication status
query   = pe

[X object 2.3.1.1.32.7.0.255]
trend = 1min
name = Volt L1
format = P:10 F:0.01
query = pe

[X snobject 2.0x1778]
trend = 1min
name = Energie total A+
format = P:10
query = pe

[X snobject 2.0x03F0]
trend = 1min
name = Energie A+ Tarif 1
format = P:10
query = pe

[X snobject 2.0x1908]
trend = 1min
name = Energie total R+
format = P:10
query = pe

[X snobject 2.0x0710]
trend = 1min
name = Energie R+ Tarif 1
format = P:10
query = pe

[X snobject 2.0xD2F8]
trend = 1min
name = Leistungsmax. A+ Tarif 1
format = P:10
query = pe

[X snobject 2.0xD618]
trend = 1min
name = Leistungsmax. R+ Tarif 1
format = P:10
query = pe

[X snobject 2.0xCBF0]
trend = 1min
name = akt. Leistungsmittel A+
format = P:10
query = pe

[X snobject 2.0xCD80]
trend = 1min
name = akt. Leistungsmittel R+
format = P:10
query = pe

[X snobject 2.0xCBF8]
trend = 1min
name = letztes Leistungsmittel A+
format = P:10
query = pe

[X snobject 2.0xCD88]
trend = 1min
name = letztes Leistungsmittel R+
format = P:10
query = pe