[M failure]
  name = Failure BACnet
  query = pe

[A local.NC 10]
  name = NC10
  bac_description = Notification Class 10
  query = pe
  bac_ack_required = (1,1,1)
  bac_priority = (10,20,30)
  bac_recipient_list = () ||WP

[S local.BI 1]
  name = Kommunikationsstörung
  query = pe
  writecache = yes
  bac_description = Kommunikationsstörung
  bac_polarity = 0
  bac_inactive_text = Normal
  bac_active_text = Störung
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[Y local.AI 4]
  name = Ist_Außenlufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_Außenlufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 5]
  name = Ist_Fortlufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_Fortlufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 6]
  name = Ist_Ablufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_Ablufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 7]
  name = Ist_Zulufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_Zulufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 8]
  name = Ist_externe Zulufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_externe Zulufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 9]
  name = Ist_externe Außenlufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_externe Außenlufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 10]
  name = Ist_externe Raumlufttemperatur
  query = pe
  writecache = yes
  bac_description = Ist_externe Raumlufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62

[Y local.AI 11]
  name = Ist_Zuluftvolumenstrom
  query = pe
  writecache = yes
  bac_description = Ist_Zuluftvolumenstrom
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135

[Y local.AI 12]
  name = Ist_Abluftvolumenstrom
  query = pe
  writecache = yes
  bac_description = Ist_Abluftvolumenstrom
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135

[Y local.AI 13]
  name = Ist_Ausgang Heizregister
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Heizregister
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 98

[Y local.AI 14]
  name = Ist_Ausgang Kühlregister
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Kühlregister
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 98

[S local.BI 15]
  name = Ist_Ausgang Vorheizregister / Solepumpe / EWT-Klappe
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Vorheizregister / Solepumpe / EWT-Klappe
  bac_polarity = 0
  bac_inactive_text = AUS
  bac_active_text = EIN
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[S local.BI 16]
  name = Ist_Ausgang Heizanforderung Kombiregister
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Heizanforderung Kombiregister
  bac_polarity = 0
  bac_inactive_text = AUS
  bac_active_text = EIN
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[S local.BI 17]
  name = Ist_Ausgang Kühlanforderung Kombiregister
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Kühlanforderung Kombiregister
  bac_polarity = 0
  bac_inactive_text = AUS
  bac_active_text = EIN
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[Y local.AI 18]
  name = Ist_Betriebsmeldung Lüftung
  query = pe
  writecache = yes
  bac_description = Ist_Betriebsmeldung Lüftung
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 95

[S local.BI 19]
  name = Ist_Ausgang Bypassklappe
  query = pe
  writecache = yes
  bac_description = Ist_Ausgang Bypassklappe
  bac_polarity = 0
  bac_inactive_text = WRG
  bac_active_text = Bypass
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[S local.MI 20]
  name = Ist_aktuelle Lüftungsstufe
  query = pe
  writecache = yes
  bac_description = Ist_aktuelle Lüftungsstufe
  bac_number_of_states = 8
  bac_state_text = ("Standby","Stufe 1","Stufe 2","Stufe 3","Grundlüftung","5","Extern Stopp","Fehler")

[S local.MI 21]
  name = Ist_aktueller Betriebsstatus
  query = pe
  writecache = yes
  bac_description = Ist_aktueller Betriebsstatus
  bac_number_of_states = 7
  bac_state_text = ("CPU startup","Standby","Anlauf","Betrieb","Nachlauf","Standby Powersafe","Testmodus")

[S local.BV 22]
  name = Para_Freigabe Heizung
  query = pe
  writecache = yes
  bac_description = Para_Freigabe Heizung
  bac_polarity = 0
  bac_inactive_text = AUS
  bac_active_text = EIN
  bac_relinquish_default = 0 -V
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[S local.BV 23]
  name = Para_Freigabe Kühlung
  query = pe
  writecache = yes
  bac_description = Para_Freigabe Kühlung
  bac_polarity = 0
  bac_inactive_text = AUS
  bac_active_text = EIN
  bac_relinquish_default = 0 -V
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[Y local.AV 24]
  name = Soll_Volumenstrom Lüftungsstufe 1
  query = pe
  writecache = yes
  bac_description = Soll_Volumenstrom Lüftungsstufe 1
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135
  bac_relinquish_default = 0 -V

[Y local.AV 25]
  name = Soll_Volumenstrom Lüftungsstufe 2
  query = pe
  writecache = yes
  bac_description = Soll_Volumenstrom Lüftungsstufe 2
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135
  bac_relinquish_default = 0 -V

[Y local.AV 26]
  name = Soll_Volumenstrom Lüftungsstufe 3
  query = pe
  writecache = yes
  bac_description = Soll_Volumenstrom Lüftungsstufe 3
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135
  bac_relinquish_default = 0 -V

[Y local.AV 27]
  name = Soll_Volumenstrom Grundlüftung
  query = pe
  writecache = yes
  bac_description = Soll_Volumenstrom Grundlüftung
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 135
  bac_relinquish_default = 0 -V

[Y local.AV 28]
  name = Soll_Zulufttemperatur
  query = pe
  writecache = yes
  bac_description = Soll_Zulufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62
  bac_relinquish_default = 0 -V

[Y local.AV 29]
  name = Soll_Raumlufttemperatur
  query = pe
  writecache = yes
  bac_description = Soll_Raumlufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62
  bac_relinquish_default = 0 -V

[Y local.AV 30]
  name = Soll_Ablufttemperatur
  query = pe
  writecache = yes
  bac_description = Soll_Ablufttemperatur
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 62
  bac_relinquish_default = 0 -V

[Y local.AI 31]
  name = Ist_CO2-Wert
  query = pe
  writecache = yes
  bac_description = Ist_CO2-Wert
  bac_resolution = 0.1
  bac_cov_increment = 0.1
  bac_units = 96

[S local.MV 33]
  name = Para_Regelungsart Temperatur
  query = pe
  writecache = yes
  bac_description = Para_Regelungsart Temperatur
  bac_number_of_states = 3
  bac_state_text = ("Abluft","Zuluft","Raumluft")
  bac_relinquish_default = 0 -V

[S local.MV 34]
  name = Soll_Betriebsmode Sommer/Winter
  query = pe
  writecache = yes
  bac_description = Soll_Betriebsmode Sommer/Winter
  bac_number_of_states = 2
  bac_state_text = ("Sommer","Winter")
  bac_relinquish_default = 0 -V

[S local.MV 35]
  name = Soll_Lüftungsstufe
  query = pe
  writecache = yes
  bac_description = Soll_Lüftungsstufe
  bac_number_of_states = 5
  bac_state_text = ("Standby","Stufe 1","Stufe 2","Stufe 3","Grundlüftung")
  bac_relinquish_default = 0 -V

[S local.BI 36]
  name = Alarm_Lüftungsgerät
  query = pe
  writecache = yes
  bac_description = Alarm_Lüftungsgerät
  bac_polarity = 0
  bac_inactive_text = Off
  bac_active_text = On
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0

[S local.BO 37]
  name = Alarm_Reset + Neustart
  query = pe
  writecache = yes
  bac_description = Alarm_Reset + Neustart
  bac_polarity = 0
  bac_inactive_text = Off
  bac_active_text = On
  bac_relinquish_default = 0 -V
  bac_feedback_value = 0
  bac_change_of_state_time = 0
  bac_change_of_state_count = 0 ||WP
  bac_time_of_state_count_reset = 0
  bac_elapsed_active_time = 0 ||WP
  bac_time_of_active_time_reset = 0